• The standards complied with are IS 13364; IS 4722; IEC 34-1; BS 4999-5000; VDE 0530; CEI 2-3; NF 51-100, 111; OVE M-10.
  • Class H insulation with the temperature rise restricted to 100°C.
  • Voltages are 380-415V at 50Hz and 440-480V at 60Hz (Y connected). Special voltages and connections can be provided on request.
  • Single phase ratings are approximately 60% of the three phase ratings.
  • Permissible overloads are:
    10% for 1 hour
    15% for 10 minutes
    30% for 4 minutes
    50% for 2 minutes
    followed by one hour of normal running.
  • The total harmonic distortion of the machine on no-load is less than 3%.
  • The voltage regulation is 1% for non-distorting loads between 0-100% (when the speed is within ± 5% of the rated speed and the power factor is between 0.8 and 1).
  • Voltage can be adjusted to ± 5% at site.
  • The transient voltage drop on application of full load at 0.8 power factor is between 15 and 20%. The output recovers to within + 3% in less than 0.6 seconds.
  • The short circuit current is greater than 3 times the rated current.
  • Motor starting of approximately I HP per kVA is possible when the AVR is used. The exact values depend on the torque characteristics, moment of inertia of the motor and the maximum acceptable voltage drop.
  • The generators have an oversized damper cage and are suitable for parallel operation when equipped with a droop transformer.
  • When the prime mover speed drops, the output voltage is reduced to prevent engine overload.
  • Initial excitation is built up using permanent magnets that are fixed on the Exciter. This ensures that the machine does not fail to develop voltage due to loss of residual magnetism.