TECHNICAL SPECIFICATIONS
Input Voltage Three Phase AC, 415 V, [+10%, -15%] Single Phase AC, 230 V, [+10%, -15%]
Frequency 50 Hz ± 5% 50 Hz ± 5%
Output Voltage Three Phase AC - 0 to input voltage
Continuous load capacity Rated current [Io] for ambient temp. up to 45oC
Over load capacity 1.5 x Io for 60 seconds for ambient temp. up to 45oC
Output Frequency 0 to 200 Hz in steps of 0.01 Hz
Constant torque: 0 to Rated Frequency
Constant power: Rated Frequency to 200 Hz
Note: Rated Frequency is programmable from 0 to 200 Hz
Environment Ambient temp. 0 to 450C
Max. chassis temp. 650C
Storage temp. -250C to 700C
Relative humidity 0 to 95% no condensation
Cooling Force cooled

SELECTION TABLE
Output KVA
AT
230V
Model No.
Max. Cont. O/P
Current
In Amps
Motor Rating
(220V, 3Ph)
kW
HP
1.6
IRAC 01 M
4.0
0.75
1.0
3.0
IRAC 02 M
7.5
1.5
2.0
Output KVA
AT
415V
Model No.
Max. Cont. O/P
Current
In Amps
Motor Rating
(415V, 3Ph)
kW
HP
1.5
ISAC 01 M
2.0
0.75
1.0
2.9
ISAC 02 M
4.0
1.5
2.0
4.0
ISAC 03 M
5.5
2.2
3.0
6.0
ISAC 05 M
8.5
3.7
5.0
9.3
ISAC 07 M
13.0
5.5
7.5
11.5
ISAC 10 M
16.0
7.5
10.0
12.9
ISAC 12 M
18.0
9.3
12.5
17.2
ISAC 15 M
24.0
11.0
15.0
23.0
ISAC 20 M
32.0
15.0
20.0
27.3
ISAC 25 M
38.0
18.5
25.0
32.3
ISAC 30 M
45.0
22.0
30.0
43.1
ISAC 40 M
60.0
30.0
40.0
51.7
ISAC 50 M
72.0
37.0
50.0
61.0
ISAC 60 M
85.0
45.0
60.0
81.9
ISAC 80 M
114.0
60.0
80.0
107.8
ISAC 100 M
150.0
75.0
100.0
129.3
ISAC 125 M
180.0
90.0
125.0
Integrated Electric Co. Pvt Ltd © Copyrights 2003 - 2004 All rights Reserved